Statement of Compliance



Environmental

Specifications Values and Remarks Compliance
Maximum ambient temperature 50 degrees YES
Minimum ambient temperature 0 degrees YES
Relative humidity levels 5%-95% YES

Electrical

Specifications Values and Remarks Compliance
Line to line and line to neutral voltage 400/230 Volts YES
Variation in line voltage (%) >1% YES
Line frequency 50 Hz YES
Variation in line frequency (%) >2% YES
Number of poles 4 poles 1500 rpm YES
Standby power KVA 22 KVA
Prime power KVA 20 KVA
Excitation method shunt YES
Power factor Not less than 80% YES
Efficiency Not Less than 92% YES
Insulation class H YES
Utilisation class H YES
Harmonic distortion <4% YES
RF emissions standards compliance
Maximum short circuit current 132 AMP
Safe short circuit duration 0.001 SEC
Long term overload 115% for 1 hour As per manufacturer recommendation 10% overload of prime power is permissible for 01 hour in a 12 Hour operations

SERVICE SPECTRUM - GENERATOR SALES


  • Deployed over 1000 gensets of 20 KVA rating on BTS sites for CMPak all over Pakistan in a very short time.
  • As a third Party Contactor supply and installation of perkins 250 kva, 300 kva and 350 kva unit in chaklala garrison Rawalpindi (SPD Building).
  • As a third party contactor Supply and installation of 3 gensets i.e 2 units of perkins 30 kva and one unit of 20 kva to 101 army aviation in 2015 peshawar.
  • Supply and installation of 2 units of 20 kva and 8 units of 5 kva in Badgram at save the children project.
  • Supply and installation of 2 gensets i.e perkins 30 kva in khuzdar at Pakistan stone development project.
  • Supply and installation of 150 kva genset in peshawar at Merlin NGO(uk) office.
  • Supply and installation of 30 kva units in Islamabad at Development in Literacy NGO office.
  • As a third party contactor Supply and installed 200 kva genset in chinar hospital PWD Rawalpindi.
  • Supply and installed AC,UPS and Genset to UN (Pops Project) Islamabad.
  • Supply and Installation of 50 kva Unit in MM ALAM road at Master showroom Lahore.
  • Deployed over 100 gensets of 30 KVA rating on the sharing sites for CMPak.
  • Deployed 45 Kva genset for ZONG on all the Customer Services Centres.
  • Deployed 100 Kva, 150 Kva, 275 Kva gensets on the Core Sites For CMPak.
  • Supply and installation of 330 KVA Genset for LinkDotNet In Lahore.
  • Supply and Installation of 100KVA, 80KVA, 25KVA, 20KVA and 10 KVA Gensets for LINKdotNet at 12 sites all over Pakistan.
  • Supply and Installation of 02 Nos 50 KVA Gensets for CMPak in Islamabad and Karachi.
  • Supply and installation of 05 Nos 100 KVA Gensets in Karachi for ASF.
  • Supply and installation of 500 Litres Extra Fuel Tank to be attached with the Gensets at different BTS Sites for CMPak.
  • Supply and Installation of 42 LCD and home theatre system at Customer Services Centres in different Cities for CMPak.

Statement of Compliance



Engine Specifications

Specifications Values and Remarks Compliance
Rated RPM 1500 rpm YES

Cooling Specifications

Specifications Values and Remarks Compliance
Water and air cooled system Water cooled YES

Exhaust Specifications

Specifications Values and Remarks Compliance
Exhaust sound filter YES

General Requirements

Specifications Values and Remarks Compliance
Provide dimensional data, loading data for civil foundation work, engine and alternator data, lubrication system data, fuel feed line data, electrical battery system data. Preferably detailed specifications sheet with this information. Data Attached with the proposal
List all standards complied with.
List of all consumables which must be kept as spares for high availability.
Generator Alarms, Safeties & Gauges YES
High engine temperature signal for shutdown YES
High alternator temperature signal for shutdown YES
High Coolant Temperature signal for shutdown YES
Low Coolant Level signal for shut down YES
Low Oil Pressure signal for shutdown YES
Over-speed signal for shutdown (Solid-state) YES
Base tank low fuel signal for shutdown YES
Oil pressure measuring Gauge YES
Engine Temperature measuring Gauge YES
Crank Limiter (Solid-state) YES
Oil Drain Extension NO (standard drain available)
Radiator Drain NO
Factory-Installed Cool Flow Radiator YES
Closed Coolant System YES
Rubber-Booted Engine Electrical Connections YES
Stainless Steel Flexible Exhaust Connection YES
Battery Charging Alternator YES
Battery Cables YES
Battery Tray YES
Battery YES
Vibration Isolation between Unit Base and Structure YES
Solenoid-activated Starter Motor YES
Air Cleaner YES
Fan Guard YES
Flexible Fuel Lines (Stainless Steel Braid) YES

Additional Features

Added Features Compliance
OPTIONAL FUEL ACCESSORIES
Primary Fuel Filters (Mounted on engine) YES
Generator base fuel tank (with local fuel gauge) YES (500 LTRS BASE FUEL TANK)
OPTIONAL ELECTRICAL ACCESSORIES
Dual Rate Battery Charger YES
Battery trickle charger for charging from mains (when generator is not running) YES
OPTIONAL ALTERNATOR ACCESSORIES
Main Line Circuit Breaker YES
OPTIONAL ENCLOSURES
Weather and sound proof canopy with enclosed critical muffler YES
ADDITIONAL OPTIONAL EQUIPMENT
Automatic Transfer Switch YES
Oil Heater YES

ATS Specifications

Specifications Compliance
Over voltage & under voltage sensing relay in ATS YES
MOR Facility in ATS YES
Image 1
Image 1
Image 2
Image 4
Image 5
Image 5
Image 5
Image 3
Image 5